This study investigated transformer loadings and failure rate in the Onitsha Electricity Distribution Network by using the Electrical Transient Analysis Program (ETAP) software 12.6 and the Statistical Package for the Social Sciences (SPSS) software 16.0....
More
This study investigated transformer loadings and failure rate in the Onitsha Electricity Distribution Network by using the Electrical Transient Analysis Program (ETAP) software 12.6 and the Statistical Package for the Social Sciences (SPSS) software 16.0. Data collected over the period 2011-2015 on the distribution network were simulated on ETAP software using the Newton-Raphson (N-R) technique to determine the transformer loadings while responses to 350 copies of questionnaire distributed among the technical staff were statistically analysed on the SPSS software to ascertain the failure rate among transformers in the network. The findings of the study show that during the 5 years period covered by the study, the sampled substations recorded transformer average failure rate of 11.7 %. It was further revealed that besides insulation issues which accounted for 24.2% of all the failures, overload (22.5%) was the next major cause of transformer breakdowns in the distribution network. The s